CVE-2014-0750

GE Proficy HMI/SCADA Path Traversal

Description

Directory traversal vulnerability in gefebt.exe in the WebView CimWeb components in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY through 8.2 SIM 24, and Proficy Process Systems with CIMPLICITY, allows remote attackers to execute arbitrary code via a crafted HTTP request, aka ZDI-CAN-1622.

Public exploit

An exploit or proof of concept is public: anyone can try it against an unpatched system. The public collections list a Metasploit module and an Exploit-DB entry for it.

Show the exploits2

Metasploit modules1 module

Exploit-DB1 entry

Modules, templates and exploits as listed by the Metasploit Framework (BSD-3-Clause), ProjectDiscovery's Nuclei templates (MIT) and the Exploit Database (GPLv2), read once a day. Where the data comes from

Timeline

  1. ID reserved

    By icscert

  2. · 23 days later

    Published

  3. · 12 years later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2014-0750, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)2.0High7.5AV:N/AC:L/Au:N/C:P/I:P/A:P
NVDNVD · Modified2.0High7.5AV:N/AC:L/Au:N/C:P/I:P/A:P
EPSS (exploitation in 30 days)
69.8% · top 0.6% of all CVEs (9 Nov 2026)
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.

Affected products

What to do

Solution: GE has produced an update that mitigates one vulnerability and made configuration changes to mitigate the other. Please reference the following GE Product Security Advisories for specific information on the vulnerabilities. GEIP13-05 To address this vulnerability, all copies of the gefebt.exe files that are accessible from a Web client must be deleted or moved, so they are inaccessible. If the production Web configuration currently relies on gefebt.exe, changes to the server’s Web pages may also be desirable. The GE Product Security Advisory, which provides additional guidance, is available here:  http://support.ge-ip.com/support/index?page=kbchannel&id=KB15939 GEIP13-06 Download Proficy HMI/SCADA - CIMPLICITY 8.2 SIM 24 at:  http://support.ge-ip.com/support/index?page=dwchannel&id=DN4128 The GE Product Security Advisory is available here:  http://support.ge-ip.com/support/index?page=kbchannel&id=KB15940