- 10.0CriticalCVSS base score
- 2.4%Exploitation in 30 daysEPSS · top 16% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier use the same RSA private key across different customers' installations, which makes it easier for remote attackers to obtain the cleartext content of network traffic by reading this key from a firmware image and then sniffing the network.
Timeline
ID reserved
By icscert
- 5 months later
· 5 months later
Published
- 11 years later
· 11 years later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| icscertCNA (assigner) | 2.0 | Critical10.0 | AV:N/AC:L/Au:N/C:C/I:C/A:C |
| NVDNVD · Modified | 2.0 | Medium5.0 | AV:N/AC:L/Au:N/C:P/I:N/A:N |
- EPSS (exploitation in 30 days)
- 2.4% · top 16% of all CVEs (10 Nov 2026)
The list uses the assigner's score when there is one, then CISA's, then NVD's: Critical 10.0.
Affected products
GE · Multilink ML800/1200/1600/2400
- affected ≤ 4.2.1
GE · ML810/3000/3100 series switch
- affected ≤ 5.2.0
What to do
Solution: GE recommends users update switch firmware to the latest published version to resolve these vulnerabilities. The new firmware will enable new keys to be calculated and exchanged, resolve the slow data transfer and potential denial of service, and prevent the identified cross-site scripting vulnerabilities. The latest firmware is Version 5.3.2 for the ML800, ML1200, ML1600 and ML2400 and Version 5.3.2-3K for the ML810, ML3000, and ML3100. This firmware is available through the “Resources/Software” link in the product web sites at http://www.gedigitalenergy.com . This firmware is also available through the EnerVista Launchpad device management tool. GE recommends updating the switch over a serial connection to prevent an attacker from capturing the new key. Please refer to the GE advisory for specific information on how to install the firmware and change RSA key. The GE advisory is available at: https://www.gedigitalenergy.com/products/support/multilink/MLSB0415.pdf
References
4
- https://www.cisa.gov/news-events/ics-advisories/icsa-15-013-04a (opens in a new tab)
- http://www.gedigitalenergy.com/products/support/multilink/MLSB1214.pdf (opens in a new tab)x_refsource_CONFIRMx_transferred
- https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2015/icsa-15-013-04a.json (opens in a new tab)
- https://ics-cert.us-cert.gov/advisories/ICSA-15-013-04 (opens in a new tab)x_refsource_MISCx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2014-5307 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2014-5419)Record last updated .