CVE-2019-13927A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web…
- 5.3MediumCVSS base score
- 1.7%Exploitation in 30 daysEPSS · top 23% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server (All firmware versions < V6.00.320). The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device's web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device's web service. While the device itself stays operational, the web server responds with HTTP status code 404 (Not found) to any further request. A reboot is required to recover the web interface. At the time of advisory publication no public exploitation of this security vulnerability was known.
Timeline
ID reserved
By siemens
- 5 months later
· 5 months later
Published
- 5 years later
· 5 years later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| NVDNVD · Modified | 3.1 | Medium5.3 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L |
- EPSS (exploitation in 30 days)
- 1.7% · top 23% of all CVEs (13 Nov 2026)
The list uses the assigner's score when there is one, then CISA's, then NVD's: Medium 5.3.
Affected products
Siemens AG · Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2
- affected All firmware versions < V6.00.320
Siemens AG · Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2
- affected All firmware versions < V6.00.320
Siemens AG · Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server
- affected All firmware versions < V6.00.320
References
References1
- https://cert-portal.siemens.com/productcert/pdf/ssa-898181.pdf (opens in a new tab)x_refsource_MISCx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2019-5197 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2019-13927)Record last updated .