CVE-2020-12526BECKHOFF: DoS-Vulnerability for TwinCAT OPC UA Server and IPC Diagnostics UA Server
- 5.3MediumCVSS base score
- 0.95%Exploitation in 30 daysEPSS · top 38% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
TwinCAT OPC UA Server in versions up to 2.3.0.12 and IPC Diagnostics UA Server in versions up to 3.1.0.1 from Beckhoff Automation GmbH & Co. KG are vulnerable to denial of service attacks. The attacker needs to send several specifically crafted requests to the running OPC UA server. After some of these requests the OPC UA server is no longer responsive to any client. This is without effect to the real-time functionality of IPCs.
Timeline
ID reserved
By CERTVDE
- 13 months later
· 13 months later
Published
- 3 years later
· 3 years later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| CERTVDECNA (assigner) | 3.1 | Medium5.3 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L |
| NVDNVD · Modified | 3.1 | Medium5.3 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L |
- EPSS (exploitation in 30 days)
- 0.95% · top 38% of all CVEs (18 Nov 2026)
The list uses the assigner's score when there is one, then CISA's, then NVD's: Medium 5.3.
Affected products
Beckhoff · TwinCAT OPC UA Server
- affected unspecified – ≤ 2.3.0.12
Beckhoff · IPC Diagnostics UA Server
- affected unspecified – ≤ 3.1.0.1
- affected unspecified – ≤ 3.3.18
What to do
Solution: For devices running Windows but not Windows CE or TwinCAT/BSD please get a recent version of the OPC UA servers through the conventional ways and update your system. For devices running Windows CE please request a recent image via Beckhoff’s support and apply it to your device. For the product CX8091 please use firmware version "CX8091_CE600_LF_v356f_TC211R3_B2306_v2" or later. Please note that the updated OPC UA server leaves less RAM available to your application on the CX8091.
Workaround: Consider disabling the IPC Diagnostics Server by stopping and disabling the corresponding Windows service or service. For example this can be achieved with the following PowerShell commands: Stop-Service -Force -Name DevMgrSvr-UA Set-Service -Name DevMgrSvr-UA -StartupType Disabled Alternatively consider limiting access to the TCP port the OPC UA server is listening on. This can happen with a dedicated firewall appliance which sits in front of an affected device. Alternatively at the device the Windows firewall can be configured to limit access to the TCP port.
References
References2
- https://cert.vde.com/en-us/advisories/vde-2020-051 (opens in a new tab)x_refsource_CONFIRMx_transferred
- https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2021-001.pdf (opens in a new tab)x_refsource_CONFIRMx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2020-4828 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2020-12526)Record last updated .