CVE-2020-6998Rockwell Automation CompactLogix 5370 and ControlLogix 5570 Controllers Improper Input Validation
- 5.8MediumCVSS base score
- 3.2%Exploitation in 30 daysEPSS · top 12% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.
Timeline
ID reserved
By icscert
- 3 years later
· 3 years later
Published
- 3 years later
· 3 years later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| icscertCNA (assigner) | 3.1 | Medium5.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:L |
| NVDNVD · Modified | 3.1 | High8.6 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H |
- EPSS (exploitation in 30 days)
- 3.2% · top 12% of all CVEs (17 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: yes · Technical impact: partial
The list uses the assigner's score when there is one, then CISA's, then NVD's: Medium 5.8.
Affected products
Rockwell Automation · Armor Compact GuardLogix 5370 controllers
- affected unspecified – ≤ versions 33 and prior
Rockwell Automation · Armor GuardLogix Safety Controllers
- affected unspecified – ≤ versions 33 and prior
Rockwell Automation · CompactLogix 5370 L1 controllers
- affected unspecified – ≤ versions 33 and prior
Rockwell Automation · CompactLogix 5370 L2 controllers
- affected unspecified – ≤ versions 33 and prior
Rockwell Automation · CompactLogix 5370 L3 controllers
- affected unspecified – ≤ versions 33 and prior
Rockwell Automation · Compact GuardLogix 5370 controllers
- affected unspecified – ≤ versions 33 and prior
Rockwell Automation · ControlLogix 5570 controllers
- affected unspecified – ≤ versions 33 and prior
What to do
Solution: Rockwell Automation recommends affected users apply firmware v33.011 or later. For more information see the Rockwell Automation advisory (login required).
References
References2
- https://www.cisa.gov/uscert/ics/advisories/icsa-21-061-02 (opens in a new tab)x_refsource_CONFIRMx_transferred
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1130398 (opens in a new tab)x_refsource_CONFIRMx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2020-28138 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket