CVE-2021-22681Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix…

Description

Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.

Exploited in the wild

CISA lists this vulnerability in its Known Exploited Vulnerabilities catalog as Rockwell Multiple Products Insufficient Protected Credentials Vulnerability.

Added
5 Mar 2026
Fix due (US federal)
26 Mar 2026
Used by ransomware
Not known

Apply mitigations per vendor instructions, follow applicable BOD 22-01 guidance for cloud services, or discontinue use of the product if mitigations are unavailable.

ENISA's EU Vulnerability Database lists it as exploited, from CISA's KEV, since 5 Mar 2026.

Public exploit

An exploit or proof of concept is public: anyone can try it against an unpatched system. CISA's SSVC rates its exploitation: it is being exploited.

Timeline

  1. ID reserved

    By icscert

  2. · 57 days later

    Published

  3. · 5 years later

    Added to CISA KEV

    Known exploited in the wild

  4. · 1 day later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2021-22681, by who scored it
Scored byCVSSScoreVector
CISA-ADPADP (enrichment)3.1Critical9.8CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
NVDNVD · Analyzed3.1Critical9.8CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS (exploitation in 30 days)
63.6% · top 0.8% of all CVEs (17 Nov 2026)
CISA SSVC
Exploitation: active · Automatable: yes · Technical impact: total
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: Critical 9.8.

Affected products

  • Rockwell Automation Studio 5000 Logix Designer, RSLogix 5000, Logix Controllers

    • affected RSLogix 5000 Versions 16 through 20
    • affected Studio 5000 Logix Designer: Versions 21 and later
    • affected CompactLogix 1768, 1769, 5370, 5380, 5480
    • affected ControlLogix 5550, 5560, 5570, 5580
    • affected DriveLogix 5560, 5730, 1794-L34
    • affected Compact GuardLogix 5370, 5380
    • affected GuardLogix 5570, 5580
    • affected SoftLogix 5800