CVE-2021-27471Rockwell Automation Connected Components Workbench Path Traversal
- 7.7HighCVSS base score
- 2.9%Exploitation in 30 daysEPSS · top 13% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
The parsing mechanism that processes certain file types does not provide input sanitization for file paths. This may allow an attacker to craft malicious files that, when opened by Rockwell Automation Connected Components Workbench v12.00.00 and prior, can traverse the file system. If successfully exploited, an attacker could overwrite existing files and create additional files with the same permissions of the Connected Components Workbench software. User interaction is required for this exploit to be successful.
Timeline
ID reserved
By icscert
- 13 months later
· 13 months later
Published
- 3 years later
· 3 years later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| icscertCNA (assigner) | 3.1 | High7.7 | CVSS:3.1/AV:L/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H |
| NVDNVD · Modified | 3.1 | High8.6 | CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H |
- EPSS (exploitation in 30 days)
- 2.9% · top 13% of all CVEs (19 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: no · Technical impact: total
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.7.
Affected products
Rockwell Automation · Connected Components Workbench
- affected unspecified – ≤ v12.00.00
What to do
Solution: Rockwell Automation recommends users of the affected software update to an available software revision (Connected Components Workbench v13.00.00 or later) that addresses the associated risk.
Workaround: Users who are unable to update are directed towards risk mitigation strategies provided below, and are encouraged, when possible, to combine these with Rockwell Automation’s general security guidelines to employ multiple strategies simultaneously. If upgrade is not possible, Rockwell Automation recommends deploying the following mitigations: Run Connected Components Workbench as a User, not as an Administrator, to minimize the impact of malicious code on the infected system. Do not open untrusted .ccwarc, files with Connected Components Workbench. Employ training and awareness programs to educate users on the warning signs of a phishing or social engineering attack. Use of Microsoft AppLocker or other similar allow list applications can help mitigate risk. Information on using AppLocker with Rockwell Automation products is available at KnowledgeBase Article QA17329 (login required). Ensure the least-privilege user principle is followed, and user/service account access to shared resources (such as a database) is only granted with a minimum number of rights as needed. For more information, please see the industrial security advisory from Rockwell Automation.
References
References2
- https://www.cisa.gov/uscert/ics/advisories/icsa-21-133-01 (opens in a new tab)x_refsource_CONFIRMx_transferred
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131435 (opens in a new tab)x_refsource_CONFIRMx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2021-14225 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2021-27471)Record last updated .