CVE-2021-35526Storage of Sensitive Information Vulnerability in Hitachi ABB Power Grids System Data Manager – SDM600 Product
- 6.3MediumCVSS base score
- 0.13%Exploitation in 30 daysEPSS · top 98% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
Backup file without encryption vulnerability is found in Hitachi ABB Power Grids System Data Manager – SDM600 allows attacker to gain access to sensitive information. This issue affects: Hitachi ABB Power Grids System Data Manager – SDM600 1.2 versions prior to FP2 HF6 (Build Nr. 1.2.14002.257).
Timeline
ID reserved
By Hitachi Energy
- 2 months later
· 2 months later
Published
- 3 years later
· 3 years later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| Hitachi EnergyCNA (assigner) | 3.1 | Medium6.3 | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:L/I:L/A:L |
| NVDNVD · Modified | 3.1 | High7.8 | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
- EPSS (exploitation in 30 days)
- 0.13% · top 98% of all CVEs (15 Nov 2026)
The list uses the assigner's score when there is one, then CISA's, then NVD's: Medium 6.3.
Affected products
Hitachi ABB Power Grids · System Data Manager – SDM600
- affected 1.2 – < FP2 HF6
What to do
Solution: The problem is remediated as of the following product version SDM600 version 1.2 FP2 HF6 (Build Nr. 1.2.14002.257). Hitachi ABB Power Grids recommends that customers apply the update at the earliest convenience. After successful upgrade it is recommended to move previously created vulnerable backups to secure place to avoid any nonauthorized access.
Workaround: It is recommended to implement and continuously revise least privileges principles to minimize permissions and accesses to SDM600 related resources. Furthermore, recommended security practices as defined in SDM600 security deployment guideline and firewall configurations can help to protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. Additional recommendation is to follow the hardening guidelines published by “The Center for Internet Security (CIS)” https://www.cisecurity.org/about-us/ to protect the host Operating System.
References
References2
- https://search.abb.com/library/Download.aspx?utm_campaign=&utm_content=2021.08_5051_Cybersecurity%20Advisory%3A&utm_medium=email&utm_source=Eloqua&DocumentID=9AKK107992A4700&LanguageCode=en&DocumentPartId=&Action=Launch&elqTrackId=ba79ef3d8aec4a4fad6c0cbe06d33d6c&elq=1bda419954724e908db108def16646a5&elqaid=3638&elqat=1&elqCampaignId= (opens in a new tab)x_refsource_CONFIRMx_transferred
- https://us-cert.cisa.gov/ics/advisories/icsa-21-250-02 (opens in a new tab)x_refsource_CONFIRMx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2021-22162 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2021-35526)Record last updated .