CVE-2022-1161ICSA-22-090-05 Rockwell Automation Logix Controllers
- 10.0CriticalCVSS base score
- 5.2%Exploitation in 30 daysEPSS · top 7.4% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
Timeline
ID reserved
By icscert
- 13 days later
· 13 days later
Published
- 3 years later
· 3 years later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| icscertCNA (assigner) | 3.1 | Critical10.0 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H |
| NVDNVD · Modified | 3.1 | Critical9.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
- EPSS (exploitation in 30 days)
- 5.2% · top 7.4% of all CVEs (16 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: yes · Technical impact: total
The list uses the assigner's score when there is one, then CISA's, then NVD's: Critical 10.0.
Affected products
Rockwell Automation · 1768 CompactLogix controllers
- affected All all
Rockwell Automation · 1769 CompactLogix controllers
- affected all
Rockwell Automation · CompactLogix 5370 controllers
- affected all
Rockwell Automation · CompactLogix 5380 controllers
- affected all
Rockwell Automation · CompactLogix 5480 controllers
- affected all
Rockwell Automation · Compact GuardLogix 5370 controllers
- affected all
Rockwell Automation · Compact GuardLogix 5380 controllers
- affected all
Rockwell Automation · ControlLogix 5550 controllers
- affected all
Rockwell Automation · ControlLogix 5560 controllers
- affected all
Rockwell Automation · ControlLogix 5570 controllers
- affected all
Rockwell Automation · ControlLogix 5580 controllers
- affected all
Rockwell Automation · GuardLogix 5560 controllers
- affected all
Rockwell Automation · GuardLogix 5570 controllers
- affected all
Rockwell Automation · GuardLogix 5580 controllers
- affected all
Rockwell Automation · FlexLogix 1794-L34 controllers
- affected all
Rockwell Automation · DriveLogix 5730 controllers
- affected all
Rockwell Automation · SoftLogix 5800 controllers
- affected all
What to do
Solution: The following mitigations should be applied for ControlLogix 5560, ControlLogix 5570, ControlLogix 5580 series, GuardLogix 5570, GuardLogix 5580, GuardLogix 5380, CompactLogix, CompactLogix 5380 devices: Risk Mitigation A: Recompile and download user program code (i.e., acd). Put controller mode switch into Run position. If keeping controller mode switch in Run is impractical, use the following mitigation: Recompile and download user program code (i.e., acd). Monitor controller change log for any unexpected modifications or anomalous activity. Utilize the Controller Log feature. Utilize Change Detection in the Logix Designer Application. If available, use the functionality in FactoryTalk AssetCenter software to detect changes. Risk Mitigation B: Implement CIP Security to help prevent unauthorized connections when properly deployed. Supported controllers and communications modules include: ControlLogix 5580 processors using on-board EtherNet/IP port. GuardLogix 5580 processors using on-board EtherNet/IP port. ControlLogix 5580 processors operating in High Availability (HA) configurations using 1756-EN4TR ControlLogix 5560, ControlLogix 5570, ControlLogix 5580, GuardLogix 5570 and GuardLogix 5580 can use a 1756-EN4TR ControlLogix EtherNet/IP module. If using a 1756-EN2T, then replace with a 1756-EN4TR CompactLogix 5380 using on-board EtherNet/IP port. CompactLogix GuardLogix 5380 using on-board EtherNet/IP port. The following mitigations should be applied for 1768 CompactLogix, 1769 CompactLogix, CompactLogix 5370, and CompactLogix 5480 devices: Recompile and download user program code (i.e., acd). Put controller mode switch into Run position. If keeping controller mode switch in Run is impractical, then use the following mitigation: Recompile and download user program code (i.e., acd). Monitor controller change log for any unexpected modifications or anomalous activity. Use the Controller Log feature. Use Change Detection in the Logix Designer application. If available, use the functionality in FactoryTalk AssetCenter to detect changes.
References
References1
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-090-05 (opens in a new tab)x_refsource_MISCx_transferred
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2022-24503 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket