CVE-2022-1667Secheron SEPCOS Control and Protection Relay

Description

Client-side JavaScript controls may be bypassed by directly running a JS function to reboot the PLC (e.g., from the browser console) or by loading the corresponding, browser accessible PHP script

Timeline

  1. ID reserved

    By icscert

  2. · 45 days later

    Published

  3. · 3 years later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2022-1667, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)3.1High7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
NVDNVD · Modified3.1High7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS (exploitation in 30 days)
1.3% · top 29% of all CVEs (12 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: yes · Technical impact: partial
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.

Affected products

What to do

Solution: Secheron recommends updating its software to the latest version: SEPCOS Single Package firmware (1.23.xx feature level): Update to 1.23.22 or higher version SEPCOS Single Package firmware (1.24.xx feature level): Update to 1.24.8 or higher version SEPCOS Single Package firmware (1.25.xx feature level): Update to 1.25.3 or higher version

Workaround: Additional workarounds are suggested to help reduce the risk: Configure the network such that PLC communications are strictly limited to only the devices required to perform its functions. Limit remote access and close Ports 80 and 443 at the switch level. Only use approved devices to connect to the PLCs. Do not connect personal peripherals (USB sticks, hotspots) to approved devices. Check device logs during periodic maintenance for unauthorized changes or access.