AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission

High7.7EPSS 0.77%
Published
Updated
Reserved
Assigned by
icscert

Description

AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;

Timeline

  1. ID reserved

    By icscert

  2. · 3 months later

    Published

  3. · 3 years later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2022-2003, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)3.1High7.7CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
NVDNVD · Modified3.1Critical9.1CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
EPSS (exploitation in 30 days)
0.77% · top 44% of all CVEs (8 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: no · Technical impact: total
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.7.

Weakness

Affected products

  • AutomationDirect · DirectLOGIC D0-06 series CPUs

    • affected D0-06DD1 – < 2.72
    • affected D0-06DD2 – < 2.72
    • affected D0-06DR – < 2.72
    • affected D0-06DA – < 2.72
    • affected D0-06AR – < 2.72
    • affected D0-06AA – < 2.72
    • affected D0-06DD1-D – < 2.72
    • affected D0-06DD2-D – < 2.72
    • affected D0-06DR-D – < 2.72

What to do

Solution: AutomationDirect recommends users upgrade to firmware Version 2.72 or later, which will no longer respond with the password when requested with the specially crafted message. Additional mitigation for brute force password access has also been added. Three incorrect password entries will result in a 3-hour lock out of password entry. Power cycle will allow subsequent password attempts. While automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application. AutomationDirect has identified the specific mitigation actions listed below: Secure physical access. Isolate and air gap networks when possible. Consider some of the AutomationDirect newer PLC families.