CVE-2022-2179

ICSA-22-188-01 Rockwell Automation MicroLogix Improper Restriction of Rendered UI Layers or Frames

Description

The X-Frame-Options header in Rockwell Automation MicroLogix 1100/1400 Versions 21.007 and prior is not configured in the HTTP response, which could allow clickjacking attacks.

Timeline

  1. ID reserved

    By icscert

  2. · 28 days later

    Published

  3. · 3 years later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2022-2179, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)3.1Medium6.5CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N
NVDNVD · Modified3.1Medium6.5CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N
EPSS (exploitation in 30 days)
1.7% · top 23% of all CVEs (12 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: no · Technical impact: partial
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: Medium 6.5.

Affected products

What to do

Workaround: Rockwell Automation encourages those using the affected software to implement the mitigations below to minimize risk. Additionally, Rockwell Automation encourages users to combine risk mitigations with security best practices (also provided below) to deploy a defense-in-depth strategy. Disable the web server where possible (this component is an optional feature and disabling it will not disrupt the intended use of the device). Configure firewalls to disallow network communication through HTTP/Port 80 If applying the mitigations noted above are not possible, please see Rockwell Automation’s Knowledgebase article QA43240 Security Best Practices. For more information, please see the industrial security advisory from Rockwell Automation.