CVE-2023-4346KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked…

Description

KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.

Exploited in the wild

CISA lists this vulnerability in its Known Exploited Vulnerabilities catalog as KNX Association KNX Protocol Connection Authorization Option 1 Overly Restrictive Account Lockout Mechanism Vulnerability.

Added
15 Jul 2026
Fix due (US federal)
29 Jul 2026
Used by ransomware
Not known

Apply mitigations in accordance with vendor instructions, ensuring compliance with CISA’s BOD 26-04 Prioritizing Security Updates Based on Risk (see URL in Notes) guidance and CISA’s “Forensics Triage Requirements” (see URL in Notes). Follow applicable BOD 26-04 guidance for cloud services or discontinue use of the product if mitigations are unavailable. Stakeholders are responsible for evaluating each asset's internet exposure and ensuring adherence to BOD 26-04 patching guidelines.

ENISA's EU Vulnerability Database lists it as exploited, from CISA's KEV, since 15 Jul 2026.

Public exploit

An exploit or proof of concept is public: anyone can try it against an unpatched system. CISA's SSVC rates its exploitation: it is being exploited.

Timeline

  1. ID reserved

    By icscert

  2. · 15 days later

    Published

  3. · 3 years later

    Added to CISA KEV

    Known exploited in the wild

  4. · 1 day later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2023-4346, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)3.1High7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
NVDNVD · Analyzed3.1High7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS (exploitation in 30 days)
1.4% · top 28% of all CVEs (12 Nov 2026)
CISA SSVC
Exploitation: active · Automatable: yes · Technical impact: partial
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.5.

Affected products

What to do

Workaround: The KNX Association recommends users always set the BCU Key in every KNX Project that is already finished and will be commissioned in the future. Handover the BCU Key as part of the Project Documentation to the Building Owner.