CVE-2024-37365FactoryTalk View ME Remote Code Execution Vulnerability via Project Save Path
- 7.0HighCVSS base score
- 0.22%Exploitation in 30 daysEPSS · top 87% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
A remote code execution vulnerability exists in the affected product. The vulnerability allows users to save projects within the public directory allowing anyone with local access to modify and/or delete files. Additionally, a malicious user could potentially leverage this vulnerability to escalate their privileges by changing the macro to execute arbitrary code.
Timeline
ID reserved
By Rockwell
- 5 months later
· 5 months later
Published
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| RockwellCNA (assigner) | 4.0 | High7.0 | CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
| RockwellCNA (assigner) | 3.1 | High7.3 | CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H |
| NVDNVD · Analyzed | 4.0 | High7.0 | CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
- EPSS (exploitation in 30 days)
- 0.22% · top 87% of all CVEs (18 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: no · Technical impact: total
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.0.
Affected products
Rockwell Automation · FactoryTalk View Machine Edition
- affected >=V14
What to do
Solution: Upgrade to Version 15
Workaround: · To enhance security and prevent unauthorized modifications to HMI project files, harden the Windows OS by removing the INTERACTIVE group from the folder’s security properties. · Add specific users or user groups and assign their permissions to this folder using the least privileges principle. Users with read-only permission can still test run and run the FactoryTalk View ME Station. · Guidance can be found in FactoryTalk View ME v14 Help topic: “HMI projects folder settings”. It can be opened through FactoryTalk View ME Studio menu “help\Contents\FactoryTalk View ME Help\Create a Machine Edition application->Open applications->HMI project folder settings”. Security Best Practices
References
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2024-36614 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2024-37365)Record last updated .