CVE-2024-6207CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and send a specially crafted…
- 8.7HighCVSS base score
- 0.55%Exploitation in 30 daysEPSS · top 53% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running.
Timeline
ID reserved
By Rockwell
- 4 months later
· 4 months later
Published
- 1 day later
· 1 day later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| RockwellCNA (assigner) | 4.0 | High8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N |
| RockwellCNA (assigner) | 3.1 | High7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| NVDNVD · Analyzed | 4.0 | High8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
- EPSS (exploitation in 30 days)
- 0.55% · top 53% of all CVEs (16 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: yes · Technical impact: partial
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 8.7.
Affected products
Rockwell Automation · ControlLogix® 5580
- affected V28.011
Rockwell Automation · ControlLogix® 5580 Process
- affected V33.011
Rockwell Automation · GuardLogix 5580
- affected V31.011
Rockwell Automation · CompactLogix 5380
- affected V28.011
Rockwell Automation · Compact GuardLogix 5380 SIL 2
- affected V31.011
Rockwell Automation · Compact GuardLogix 5380 SIL 3
- affected V32.013
Rockwell Automation · CompactLogix 5480
- affected V32.011
Rockwell Automation · FactoryTalk® Logix Echo
- affected V33.011
What to do
Solution: AFFECTED PRODUCTS AND SOLUTION Affected Product First Known in firmware revisionCorrected in firmware revisionControlLogix® 5580V28.011V33.017, V34.014, V35.013, V36.011 and laterControlLogix® 5580 ProcessV33.011V33.017, V34.014, V35.013, V36.011 and laterGuardLogix 5580V31.011 V33.017, V34.014, V35.013, V36.011 and laterCompactLogix 5380V28.011 V33.017, V34.014, V35.013, V36.011 and laterCompact GuardLogix 5380 SIL 2V31.011V33.017, V34.014, V35.013, V36.011 and laterCompact GuardLogix 5380 SIL 3V32.013V33.017, V34.014, V35.013, V36.011 and laterCompactLogix 5480V32.011V33.017, V34.014, V35.013, V36.011 and laterFactoryTalk® Logix Echo V33.011V34.014, V35.013, V36.011 and later
References
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2024-47344 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2024-6207)Record last updated .