CVE-2024-6242Rockwell Automation Chassis Restrictions Bypass Vulnerability in Select Logix Devices

Description

A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis.

Timeline

  1. ID reserved

    By Rockwell

  2. · 41 days later

    Published

  3. · 14 months later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2024-6242, by who scored it
Scored byCVSSScoreVector
RockwellCNA (assigner)4.0High7.3CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H
NVDNVD · Deferred4.0High7.3CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
EPSS (exploitation in 30 days)
11.1% · top 4.0% of all CVEs (18 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: no · Technical impact: total
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 7.3.

Affected products

What to do

Workaround: Affected Product First Known in Firmware Revision Corrected in Firmware Revision ControlLogix® 5580 (1756-L8z) V28 V32.016, V33.015, V34.014,   V35.011 and later   GuardLogix® 5580 (1756-L8zS) V31 V32.016, V33.015, V34.014,   V35.011 and later 1756-EN4TR V2 V5.001 and later 1756-EN2T, Series A/B/C 1756-EN2F, Series A/B 1756-EN2TR, Series A/B 1756-EN3TR, Series B v5.007(unsigned)/v5.027(signed) No fix is available for Series A/B/C. Users can upgrade to Series D to remediate this vulnerability 1756-EN2T, Series D 1756-EN2F, Series C 1756-EN2TR, Series C 1756-EN3TR, Series B 1756-EN2TP, Series A 1756-EN2T/D: V10.006 1756-EN2F/C: V10.009 1756-EN2TR/C: V10.007 1756-EN3TR/B: V10.007 1756-EN2TP/A: V10.020 V12.001 and later Users using the affected firmware and who are not able to upgrade to one of the corrected versions are encouraged to apply the following mitigation and security best practices, where possible.    * Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position. * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight

References

References1

Sources

The same CVE in the primary databases and aggregators, to check against.

Badge for a README or a ticket

CVE-2024-6242 badge
[![CVE-2024-6242](https://cveledger.app/badge/CVE-2024-6242.svg)](https://cveledger.app/cve/CVE-2024-6242)

Record last updated .