CVE-2025-40944
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF…
- 8.7HighCVSS base score
- 0.44%Exploitation in 30 daysEPSS · top 62% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
Timeline
ID reserved
By siemens
- 9 months later
· 9 months later
Published
- 5 months later
· 5 months later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| siemensCNA (assigner) | 4.0 | High8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N |
| siemensCNA (assigner) | 3.1 | High7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| NVDNVD · Deferred | 4.0 | High8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
- EPSS (exploitation in 30 days)
- 0.44% · top 62% of all CVEs (12 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: yes · Technical impact: partial
The list uses the assigner's score when there is one, then CISA's, then NVD's: High 8.7.
Affected products
Siemens · SIMATIC ET 200AL IM 157-1 PN
- affected < *
Siemens · SIMATIC ET 200MP IM 155-5 PN HF
- affected V4.2.0 – < *
Siemens · SIMATIC ET 200SP IM 155-6 MF HF
- affected < *
Siemens · SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)
- affected < V1.3
Siemens · SIMATIC ET 200SP IM 155-6 PN R1
- affected < V6.0.1
Siemens · SIMATIC ET 200SP IM 155-6 PN/2 HF
- affected V4.2.0 – < V4.2.5
Siemens · SIMATIC ET 200SP IM 155-6 PN/3 HF
- affected < V4.2.2
Siemens · SIMATIC PN/MF Coupler
- affected < *
Siemens · SIMATIC PN/PN Coupler
- affected < V6.0.0
Siemens · SIPLUS ET 200MP IM 155-5 PN HF
- affected V4.2.0 – < *
Siemens · SIPLUS ET 200MP IM 155-5 PN HF
- affected V4.2.0 – < *
Siemens · SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL
- affected V4.2.0 – < *
Siemens · SIPLUS ET 200SP IM 155-6 PN HF
- affected V4.2.0 – < V4.2.5
Siemens · SIPLUS ET 200SP IM 155-6 PN HF
- affected V4.2.0 – < V4.2.5
Siemens · SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL
- affected V4.2.0 – < V4.2.5
Siemens · SIPLUS ET 200SP IM 155-6 PN HF TX RAIL
- affected V4.2.0 – < V4.2.5
Siemens · SIPLUS NET PN/PN Coupler
- affected < V6.0.0
References
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2026-2359 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2025-40944)Record last updated .