CVE-2026-4436GPL Odorizers GPL750 Missing Authentication for Critical Function

Description

A low-privileged remote attacker can send Modbus packets to manipulate register values that are inputs to the odorant injection logic such that too much or too little odorant is injected into a gas line.

Timeline

  1. ID reserved

    By icscert

  2. · 21 days later

    Published

  3. · 5 days later

    Record updated

Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.

Scores

CVSS scores of CVE-2026-4436, by who scored it
Scored byCVSSScoreVector
icscertCNA (assigner)3.1High8.6CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:N
NVDNVD · Awaiting Analysis3.1High8.6CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:N
EPSS (exploitation in 30 days)
0.46% · top 60% of all CVEs (16 Nov 2026)
CISA SSVC
Exploitation: none · Automatable: yes · Technical impact: partial
Loading the EPSS history…

The list uses the assigner's score when there is one, then CISA's, then NVD's: High 8.6.

Affected products

What to do

Solution: GPL Odorizers recommends users update to the latest software version of the GPL750 in connection with the latest firmware from Horner Automation for the XL4, XL4 Prime, XL7, and XL7 Prime devices.https://lincenergysystems-my.sharepoint.com/:f:/p/h_baer/IgDYaHIhXpyLQJvnKPd6b80TAUgV7Lp8qmVYBFUb0lmr7ak?e=JLeADm. https://lincenergysystems-my.sharepoint.com/:f:/p/h_baer/IgDYaHIhXpyLQJvnKPd6b80TAUgV7Lp8qmVYBFUb0lmr7ak?e=JLeADm

Solution: GPL Odorizers recommends users clear the old files from their microSD cards, keeping only the LOGS folder and the FIRMWARE.LIC file if they have a WebMI license. The compressed folder downloaded from the link above can then be extracted to the root directory of the microSD card. These files already include the corresponding firmware update. If users do not have IT permissions to access their microSD cards, GPL Odorizers can provide preconfigured SD cards that technicians can simply swap into their odorizers prior to installation.

Solution: For assistance in updating GPL Odorizers to the latest version, users should reach out to GPL Odorizers directly via phone number (303) 697-6701 during the hours of 8:00 a.m. to 4:00 p.m. MST.

Solution: Horner Automation offers firmware version 15.76 for their XL Series and version 17.30 for their XL Prime Series controllers. An installation guide is available for both the XL series and the XL Prime series. https://hornerautomation.com/controller-firmware/