CVE-2026-61884Tycon Systems TPDIN-Monitor-WEB2 Missing Authentication for Critical Function
- 9.3CriticalCVSS base score
- 0.56%Exploitation in 30 daysEPSS · top 53% of all CVEs
- NoKnown exploitednot in CISA's KEV catalog
- NonePublic exploitsnone known yet
Description
The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.
Timeline
ID reserved
By icscert
- 11 days later
· 11 days later
Published
- 42 days later
· 42 days later
Record updated
Changes after publication (a new score, a public exploit, EPSS crossing 1, 10 or 50 %, leaving KEV) are kept since November 2026; earlier ones are not known.
Scores
| Scored by | CVSS | Score | Vector |
|---|---|---|---|
| icscertCNA (assigner) | 4.0 | Critical9.3 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
| icscertCNA (assigner) | 3.1 | Critical9.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
| NVDNVD · Deferred | 4.0 | Critical9.3 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
- EPSS (exploitation in 30 days)
- 0.56% · top 53% of all CVEs (14 Nov 2026)
- CISA SSVC
- Exploitation: none · Automatable: yes · Technical impact: total
The list uses the assigner's score when there is one, then CISA's, then NVD's: Critical 9.3.
Affected products
Tycon Systems · TPDIN-Monitor-WEB2
- affected < 2.4.5
- unaffected 2.4.5
What to do
Solution: Tycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to [email protected]. Tycon Systems recommends setting an administrative username and strong password on the Network Configuration page and confirming in a private browser window that a login is required, for units still running firmware 2.4.4 or earlier. Repeat this after any factory reset. Tycon Systems recommends not exposing the web interface to the Internet, as it is HTTP only. The unit should be kept on a private network, behind a firewall or VPN.
References
Sources
The same CVE in the primary databases and aggregators, to check against.
- CVE.org record (opens in a new tab)
- CVE List JSON (GitHub) (opens in a new tab)
- NVD (opens in a new tab)
- FIRST EPSS (opens in a new tab)
- EUVD EUVD-2026-48745 (opens in a new tab)
- OSV.dev (opens in a new tab)
- GitHub Advisories (opens in a new tab)
- CIRCL Vulnerability-Lookup (opens in a new tab)
Badge for a README or a ticket
[](https://cveledger.app/cve/CVE-2026-61884)Record last updated .